111. Ventilation of change rooms and toilets: During the hours of operation of an establishment, the change rooms and washrooms shall be ventilated toward the outside of the establishment, either naturally in accordance with section 102, or mechanically by extraction in accordance with the standards prescribed in the following table:

________________________________________________________________

Place Ventilation (in cubic
metres of air per hour)

________________________________________________________________

Change hooks or lockers 18 m3/h per square
rooms for street clothes metre of the room’s
or unsoiled work surface area.
clothes
_______________________________________________

hooks or lockers the greater of:
for damp work 36 m3/h per square
clothes (drying metre of the room’s
facilities) surface area, and
12 m3/h per locker.
________________________________________________________________

Toilets and the greater of:
urinals - 36 m3/h per square
metre of the room’s
surface area, and
- 45 m3/h per toilet
or urinal, but not less
than 350 m3/h.
________________________________________________________________

Showers the greater of:
- 36 m3/h per square
metre of the room’s
surface area, and
- 90 m3/h per shower
head, but not less than
350 m3/h.
________________________________________________________________
Where a washroom is ventilated naturally, the ventilation area per toilet shall be 0.1 m2.
O.C. 885-2001, s. 111.